Linesense H8028
LINEAR HEAT DETECTION (LHD)
(105°C, 221°F Nominal)
The technology behind the digital Linear Heat Detection (LHD) cable, makes it a product of choice for difficult and challenging applications where other technologies may struggle.
It is easy to install and requires low maintenance therefore providing a cost effective solution where project expenditure requires to be kept at a minumum.
The sensing cable is created from a pair of twisted steel conductors, with temperature sensitive insulation. And an overal PVC outer sleeve. When the temperature sensitive insulation reaches it's predetermined alarm temperature the two conductors short together providing the digital or switched signal.
The LHD cable can be connected to any unit monitoring a switched signal, i.e. Conventional fire panel, addressable switch monitor unit or PLC.
The PVC outer sleeve of the Linesense H8028N offers good UV resistance, allowing it to be deployed in external applications.
Features
- Simple digital switch operation.
- Continuous sensing along the total length of the element.
- Fixed alarm temperature operation.
- Compatible with switch monitoring units.
- Suitable for use in Hazardous areas.
- UV resistant PVC outer sleeve.
- Rugged and durable construction.
- Simple maintenance free installation.
- Small diameter and bend radius.
- FM Approved.
Applications
- Conveyors / bearing Protection.
- Escalators, moving walkways.
- Cable tunnel / tray protection.
- Road and rail tunnels.
- Road and rail motor compartments.
- Electrical switch gear & transformers.
- Refrigerated rooms and cold stores.
- Building exteriors under eaves.
- Motor and pump overheat detection.
- Dirty and dusty environments.
Technical Data
Specifications
Alarm temperature: |
105°C |
Max amb temperature: |
70°C |
Min operating temperature: |
-30°C |
Min installation temperature: |
0°C |
Electrical
Resistance: |
100 ohms / Km @ 20°C |
Capacitance: |
45 pF/m to 130 pF/m |
Inductance: |
0.74 ųH/m to 1.3 uH/m |
Voltage rating: |
110vdc 1amp |
Time to detect a small flame: |
12 sec (Flame touching) |
Mechanical
Outside diameter: |
4.25mm |
Colour: |
Black |
Number of cores: |
2 |
Core diameters: |
0.9mm |
Core colours: |
Black and red |
Minimum bend radius: |
50mm (Cold store 100mm) |
Weight: |
25.0Kg/Km on the reel (weight of reel typically 2Kg) |
Ordering Info
Part Number |
Description |
51100-105 |
Linesense H8028N sensing cable 105°C Alarm temperature Black PVC outer sleeve. (ordered by the meter) |
Optional |
|
52100-001 |
|
52100-002 |
|
52101-001 |
DIM Digital Interface Module DIN rail mounted |
53000-001 |
Portable test oven 1m |